Posted By Will Weiwen Huang Aug 15, 2023 11:07:59 PM
Found In Egroup: Advanced Software
\ view thread
Hi Joe, Welcome to Rockwell Automation Community ! The HmiPingAgent is an HMI server agent responsible for monitoring the health of the core HMI server components. The Rockwell Redundancy Service (RdcyHost.exe) will load the HmiPingAgent.dll during initialization. The error "HmiPingAgent,RTE_Err ...
Posted By Will Weiwen Huang Aug 15, 2023 10:38:31 PM
Found In Egroup: Advanced Software
\ view thread
Hi Melo, Welcome to Rockwell Automation Community ! The Adobe Flash Player is used for viewing multimedia contents by RSLogix 5000/Studio 5000 Online Books. If Adobe Flash Player is uninstalled, it will prevent user from viewing those but will not effect the software running. Please refer to RA KB ...
Posted By Will Weiwen Huang Aug 09, 2023 09:28:00 PM
Found In Egroup: Advanced Software
\ view thread
Hi Chinnaiah, Welcome to Rockwell Automation Community ! Regarding the PLC string tag no data reading from SQL via FTTM transaction, it should be caused by that the .LEN field of string tag does not automatically get updated while writing the CLX STRING data type via FTTM. To workaround this shortcoming, ...
Posted By Will Weiwen Huang Jul 30, 2023 11:03:00 PM
Found In Egroup: Advanced Software
\ view thread
Hi Jake, You may use the following VBA script: ExecuteCommand "Language en-US" For more detail, please refer to RA KB FactoryTalk View SE Software: Trigger Commands on Client from HMI Server Hope it will be working for you. ------------------------------ Will Weiwen Huang ---------------- ...
Posted By Will Weiwen Huang Jul 26, 2023 03:40:00 AM
Found In Egroup: Advanced Software
\ view thread
Hi Jake, Welcome to Rockwell Automation Community ! To pass Button Caption text as a global parameter, you may Insert Variable in the Caption field and use the Literal String setting and enter the global parameter placeholder, e.g. #101. Unfortunately, Global Object Parameter Values does ...
Posted By Will Weiwen Huang Jul 13, 2023 09:15:00 PM
Found In Egroup: Advanced Software
\ view thread
EDIT: corrected link as it was badly shown in the post -FL Hi Tomek, The particular patch is Patch: RecipePro+ Editor and List taking longer to load, FactoryTalk View SE 10.0, 11.0, 12.0, 13.0 . It is not exactly match your case however it should fix some RecipePro+ performance issue so it is worth ...
Posted By Will Weiwen Huang Jul 13, 2023 01:49:26 AM
Found In Egroup: Advanced Software
\ view thread
Hi Tomek, Thank you for the reply. There is a patch released at Jan 2023 to fix RecipePro+ loading issue for FTView SE v11. Could you please download the latest RA Patch Rollup and install it on all the FT View server/clients and FT Directory machines. If problem persists, you need contact RA ...
Posted By Will Weiwen Huang Jul 10, 2023 08:32:18 PM
Found In Egroup: Advanced Software
\ view thread
Hi Tomek, Welcome to Rockwell Automation Community ! Regarding the FTView SE Recipe pro+ recipe problem, more information are required for troubleshooting: The version of FTView SE and FactoryTalk Service Platform The level of RA Patch Rollup installed Is it FTView SE local application or Distributed ...
Posted By Will Weiwen Huang May 15, 2023 10:36:00 PM
Found In Egroup: Advanced Software
\ view thread
Hi Bahaa, Welcome to Rockwell Automation Community ! Regarding the FTGW v6.31 issue, please note that the RA patch rollup Nov.2022 does not include any patch for FT Service v6.31 and FTGW v6.31. Inthis case, please upgrade to the latest RA Patch Apr.2023. Also, if the FT Ntework Directory server ...
Posted By Will Weiwen Huang Apr 10, 2023 11:23:00 PM
Found In Egroup: Networks
\ view thread
Hi Kiran, Welcome to Rockwell Automation Community ! Regarding the access to the remote PLC on different networks, if it is able to ping the Lan Network - 02 PLC on Server PC 01 , you may setup RSLinx Classic Ethernet Device driver on Server PC 01 and add the IP address of the Lan Network - 02 ...
Posted By Will Weiwen Huang Feb 06, 2023 06:13:00 PM
Found In Egroup: Advanced Software
\ view thread
Hi Ricardo, Welcome to Rockwell Automation Community ! Currently, there is not utility/tools to convert a TIA Portal HMI project (TP1200, MTP1200, PC RT) Siemens to FactoryTalk View. Please refer to RA KB Conversion from third party HMI product to FactoryTalk View SE for more detail. Thanks ...
Posted By Will Weiwen Huang Jan 23, 2023 11:38:00 PM
Found In Egroup: Advanced Software
\ view thread
Hi Maynard, It was nice speaking to you over the phone. As per our discussion, each FTTM Transaction can be only working with one Data Object. Need create a new transaction for the other Dat Object. Thanks and Regards, Will Huang Consultant Engineer Remote Support | Asia Pacific Rockwell ...
Posted By Will Weiwen Huang Jan 22, 2023 07:03:00 PM
Found In Egroup: Advanced Software
\ view thread
Hi Zion, Welcome to Rockwell Automation Community ! Regarding the FT Metrics upgrade, the uninstallation of older version is required and it will NOT remove the existing configuration since all configuration are stored in SQL database. Just in case, you may backup the RSBizware SQL Server database ...
Posted By Will Weiwen Huang Nov 25, 2022 02:59:00 AM
Found In Egroup: Advanced Software
\ view thread
Hi Micah, Welcome to Rockwell Automation Community ! Regarding PlantPAx PVSD Fault Code List Functionality and Display, you need enable the alarm for Device Fault in PVSD Properties and the fault code and description will be shown in the alarm message as below: Also, remember to enable ...
Posted By Will Weiwen Huang Sep 04, 2022 09:10:00 PM
Found In Egroup: Advanced Software
\ view thread
Hi Fernando, Welcome to Rockwell Automation Community ! Regarding the issue of zoom in the second time opening the trend, as per the screenshot, it seemed the popup display was resized at the second open. To solve this issue, please refer to the RA KB ID: BF4663 - FactoryTalk View SE: Popup display ...
Posted By Will Weiwen Huang Jul 22, 2022 01:38:00 AM
Found In Egroup: Advanced Software
\ view thread
Hi Andrei, Welcome to the Forum ! The server-side powershell scripts in v12 cannot achieve the automated DatalogMergeToPrimary because it cannot trigger an FTVIew SE Command. The simple workaround is, as you mentioned, perform Datalog Merge periodically. If it is ODBC based Datalog, the DatalogDataMergeTool ...
Posted By Will Weiwen Huang Feb 27, 2022 08:40:00 PM
Found In Egroup: Advanced Software
\ view thread
Hi GRO, Thanks for your reply. As I mentioned before, the networking issue may cause expected delay of SE client login. For more detail, please refer to RA KB: https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1127279 Hope it will clarify your query. Best Regards, Wi ...
Posted By Will Weiwen Huang Feb 24, 2022 07:18:00 PM
Found In Egroup: Advanced Software
\ view thread
Hi GRO, Thanks for your reply. It is not necessary to downgrade the RNASecurity.dll because the higher version should included all the fix of lower version so the machine should be patched. In general, the networking issue may cause expected delay of SE client login. Could you try to disable ...
Posted By Will Weiwen Huang Feb 23, 2022 06:06:00 PM
Found In Egroup: Advanced Software
\ view thread
Hi GRO, Thank you for your post. In general, the FTView SE Client will try to reach FT Directory Server at the initial login. If cannot connect to FTD server after certain timeout, the local FTD cache will be in used. There is no way to set the Authentication to always use local FTD cache. Also, ...
Posted By Will Weiwen Huang Feb 06, 2022 10:10:00 PM
Found In Egroup: Automation Control
\ view thread
Hi Camille, Thank you for your update. For further assistance, is it possible to send us the FTView ME project APA backup file? I will try to reproduce the issue in my VM. Thanks and Regards, Will