Okay finally answered my own question. HSCCMD must be a valid number prior to enabling the HSC block - therefore before your HSC rung (& via utilizing initial values) you'll want to write between a 1 & 4 in order to prevent controller faults. Yeesh that one is sneaky.
Posted By Langevin Aug 26, 2024 11:36:55 AM
Found In Egroup: Automation Control
\ view thread
More to Add here after some testing: If after a download, while the controller is in faulted state & not yet cleared, I can reinput the application setting for "OFSetting" & the PLC will go into run mode without fault & HSC will operate correctly. It's almost as if the header file isn't dumping initial ...
Posted By Langevin Aug 26, 2024 11:07:00 AM
Found In Egroup: Automation Control
\ view thread
Hi All, Scratching my head on this one. On download the controller faults 0xF840, which can be cleared & ran. Afterwards the HSC block appears to be running without error but does not count correctly (definitely not high-speed). I have configured HSCs with similar settings & exact same controller/FW ...