Posted By
Beck
Jan 29, 2024 01:09:00 PM
Found In
Egroup:
Automation Control
\
view thread
I have a 5069 remote IO rack with 10 cards, the chassis size is set to 11. The connection between the PLC and the AENTR is working but I have the following error on each SAFETY card. Error code 16#0312 Connection Request Error: Invalid link address. I have checked the MOD and SA power both have 24vdc. ...
|