Posted By Shawn Jun 30, 2026 06:10:00 AM
Found In Egroup: Automation Control
\ view thread
Ajay, Upon further investigation, I discovered they replaced the ENET with an ENBT that had a firmware version of 4.3. We were later able to stumble across a website that provided my solution. Upgrading the ENBT's firmware to higher version fixed my issue and I now have steady communications and control. ...
Posted By Shawn Jun 29, 2026 04:36:00 PM
Found In Egroup: Automation Control
\ view thread
I'm not having good luck getting any of the ArmorBlock 1732E-16CFGM12QCR to talk to the 1756-L63E PLC through a 1756-ENET/B Ethernet Communications Interface. ArmorBlock > Version 3.012 Verison 20.19 Version 2.1 RS-Linx sees the ArmorBlocks just fine and I'm able to ping each one successfully. ...
Posted By Shawn Mar 20, 2026 10:16:00 AM
Found In Egroup: Automation Control
\ view thread
Thanks for the response, DSTC If I don't check out the file, Studio 5000 is smart enough to realize it's locked and prompts me to open a copy. In that case, the WRK and SEM files aren't created. If I do check it out, the program opens normally and the WRK and SEM files are created. In both cases, ...
Posted By Shawn Mar 18, 2026 10:32:17 AM
Found In Library: Automation Control
Posted By Shawn Mar 18, 2026 10:32:00 AM
Found In Egroup: Automation Control
\ view thread
I too have had problems with using Studio 5000 when opening files from a SolidWorks PDM. My files will open normally, but as soon as I try to open a routine, Studio 5000 crashes and gives fatal error codes. I decided to instead start storing our programs onto a share network drive instead that wasn't ...