Posted By Steve Radel Jan 23, 2024 07:04:52 AM
Found In Egroup: Automation Control
\ view thread
If you haven't already done so, use RSLogix 500 v12 to do the conversion. ------------------------------ Stave Radel Senior Engineer, Remote Support Rockwell Automation ------------------------------
Posted By Steve Radel Jan 27, 2023 06:38:00 AM
Found In Egroup: Legacy
\ view thread
Hi Ryan, It looks like you are getting overflows in those registers. If a math operation is performed and the result is too big or small for the register, a -32,768 or 32768 will be written into the register and the Math Overflow Trap (S:5/0) will be set. This will normally fault the controller with ...
Posted By Steve Radel Jan 13, 2023 02:55:00 PM
Found In Egroup: Legacy
\ view thread
A solid COMM1 indicator means the controller is transmitting via the Ethernet port (Channel 1). This is normal operation. Please go online over RS232 and check the Channel 1 IP address, configuration and status. This should give you some idea of what is happening. ------------------------------ Please ...
Posted By Steve Radel Oct 07, 2022 07:00:00 AM
Found In Egroup: Automation Control
\ view thread
Both ports support device-level networks, however only port 1 can support an enterprise level network. Both ports can be used for programming. Also, CIP bridging for Class 3 CIP messages between the two separate networks is supported. ------------------------------ Please Like the replies that you ...
Posted By Steve Radel Jan 13, 2022 08:46:00 AM
Found In Egroup: Automation Control
\ view thread
Hi Kurt, The ABSOCODER encoder is an absolute encoder. The VM-2A(MRE) is a signal converter that takes the "raw" signal from the encoder sensor and converts it to a 16-bit binary (or 16-bit gray binary) driver signal that can be consumed by a digital PLC input module. Unfortunately, this converter ...