Posted By PT Feb 15, 2026 02:39:48 PM
Found In Egroup: Automation Control
\ view thread
Hi, Thanks for the detailed explanation! I chaned the write command as event baswd and thankfully the delay has been reduced to 3seconda which is acceptable for client. Also we will try to split the loop so that no. of devices can be reduced in one loop. Thanks sandeep ------------------- ...
Posted By PT Feb 14, 2026 02:12:00 PM
Found In Egroup: Automation Control
\ view thread
Hello Philip, I have done the configuration in PLX31 and CLX. I tested the application with one actuator and its working well but the only issue is its updating very slow ie 10sec, because I have configured around 50 devices in prosoft module for read/write operations which is around 100 commands. ...
Posted By PT Feb 14, 2026 02:11:54 PM
Found In Library: Automation Control
Posted By PT Feb 10, 2026 09:59:57 AM
Found In Egroup: Automation Control
\ view thread
Hello Philip, I have tested prosoft with clx via msg instruction and its working well.. I will do some data mapping from both gateways and further logic will do to asses the channel healthiness for redundancy. Since the existing program is in RSlogix 5K V15,, is there any chance to get a demo ...
Posted By PT Feb 05, 2026 09:50:48 AM
Found In Egroup: Automation Control
\ view thread
Sure I will go through the document! and both are active channel and SIMA system is controlling the commands ie -------------------------------------------
Posted By PT Feb 05, 2026 06:01:52 AM
Found In Library: Automation Control
Posted By PT Feb 05, 2026 06:01:52 AM
Found In Egroup: Automation Control
\ view thread
Hello Philip, Sorry as I could not make it clear , please find below with detail Current Configuration: There are approximately 50 AUMA actuators in the field. Each actuator is connected via two separate Modbus channels (Channel A and Channel B) -two independent rs485 cable from field These ...
Posted By PT Feb 04, 2026 12:13:00 PM
Found In Egroup: Automation Control
\ view thread
Hi, I have around 50actuators with Dual channel modbus RS485 communication ie Channel A and ChannelB. I will use two PLX31 and connect each channels to them. Since the processor firmware is old I will have to use the msg instruction to read the registers of PLX31 to processor. In this case can ...