Posted By Francis Audet Dec 12, 2023 09:08:00 AM
Found In Egroup: Automation Control
\ view thread
To follow up on the problem we had, it was determined that it was because the integrator, who built the cell, was (physically) cutting the 24VDC on the outputs in addition to turning the outputs off. We had the safety side of the cell analyzed to see if we could stop physically cutting the 24v outputs ...
Posted By Francis Audet Nov 03, 2022 12:20:00 PM
Found In Egroup: Automation Control
\ view thread
I will plan to upgrade to 15.2(7)E or later for sure Same for 1732ES Armorblock but I have an issue right now to download the last revision on RA website. I have open a ticket for that issue. But like you said in a earlier post, ------------------------------ Francis Audet ------ ...
Posted By Francis Audet Nov 03, 2022 09:28:00 AM
Found In Egroup: Automation Control
\ view thread
Hi, Following a discussion on a previous post, I want to do a firmware upgrade on an I/O block from the 1732ES family. Has anyone done this before? What tools did you use? Thank you! ------------------------------ Francis Audet ------------------------------
Posted By Francis Audet Nov 03, 2022 09:24:00 AM
Found In Egroup: Automation Control
\ view thread
Hello James, We use Allen Bradley RFID Tag familly here, and we have no complaints about the product. We use 56RF-TG-50MOM tags mounted on our production dollies (they have the capability to be Mounted On Metal). These dollies are traveling throught washer machine, paint shop and oven without any problem. ...
Posted By Francis Audet Nov 03, 2022 07:08:00 AM
Found In Egroup: Automation Control
\ view thread
Here is our Firmware Revision... ------------------------------ Francis Audet ------------------------------
Posted By Francis Audet Nov 03, 2022 06:32:00 AM
Found In Egroup: Automation Control
\ view thread
See my answers in Bold letters below I assume the Wireshark was from a port mirror on port 12? YES it is It seems we have multiple clues to indicate the 1732ES is rebooting: LED indicators on 1732ES We will try to capture this with a camera Wireshark traffic abruptly ends, restarts ...
Posted By Francis Audet Nov 02, 2022 01:25:00 PM
Found In Egroup: Automation Control
\ view thread
Like you said, the IPDT is suppose to be available on all the armorstratix 5700 (like it stated in the user manual) but I don't have the option available on mine??? I don't know if it can be the root cause of our problem... User Manual Our Armorstratix ------------------------------ Francis ...
Posted By Francis Audet Nov 02, 2022 12:41:00 PM
Found In Egroup: Automation Control
\ view thread
Philip, We already take a look to that tech note about that maximum messages limit. But we are not communicating with that I/O block by MSG instruction so I don't think it is apply to our case. Maybe an update of the firmware can still help us? I saw on RA Website that the version 1.012 is the ...
Posted By Francis Audet Nov 02, 2022 12:24:00 PM
Found In Egroup: Automation Control
\ view thread
As you can see on the image below, there are 4 devices connected to port 12 of the switch (all in daisy chain). 10.64.68.47 et.48 (1732 ES Safety I/O blocks) 10.64.68.49 and .50 (Lenze Drives) When we loose communication with the 1st or 2nd device in the chain, we also lose communication with downstream ...
Posted By Francis Audet Nov 02, 2022 10:13:17 AM
Found In Library: Automation Control
Posted By Francis Audet Nov 02, 2022 10:13:00 AM
Found In Egroup: Automation Control
\ view thread
Here is the zip file I sent to Philip It will be attach to the discussion now Thank you @fuzzy logic​ ------------------------------ Francis Audet ------------------------------
Posted By Francis Audet Nov 01, 2022 01:19:00 PM
Found In Egroup: Automation Control
\ view thread
Hi Philip, I try to include a copy of the wireshark capture we were able to make this morning when communication was lost with one of our 1732 ES blocks. I can't insert the file here because is not a "supported files" I will send you the file for analysis. On line #202908, I believe this is where ...
Posted By Francis Audet Oct 28, 2022 11:53:00 AM
Found In Egroup: Automation Control
\ view thread
Thank you Philip, I will try to capture, using WireShark, what happens a little before, and at the time of the loss of communication, and come back to you with the details. ------------------------------ Francis Audet ------------------------------
Posted By Francis Audet Oct 27, 2022 12:43:00 PM
Found In Egroup: Automation Control
\ view thread
Thank you Philip, What does T-Specs means? I assume that pps is for Packet Per Second? So, if I understand correctly, this means that this module (1732ES) is not as sensitive to loss of connections as a 525 drive? ------------------------------ Francis Audet ----------------------------- ...
Posted By Francis Audet Oct 27, 2022 07:09:00 AM
Found In Egroup: Automation Control
\ view thread
Thank you for the feedback We will try this! Francis ------------------------------ Francis Audet ------------------------------
Posted By Francis Audet Oct 27, 2022 07:03:11 AM
Found In Library: Automation Control
Posted By Francis Audet Oct 27, 2022 07:03:00 AM
Found In Egroup: Automation Control
\ view thread
Good morning Ryan, Thank you for your quick reply Here is my answers to your questions in underline below. Is this a new system or a new issue on a system that has been running for a while?: It's a new build cell running since july 2021 . That problem was there at the begining but with the increase ...
Posted By Francis Audet Oct 26, 2022 12:01:00 PM
Found In Egroup: Automation Control
\ view thread
We have several 1732ES modules that randomly lose communication with the safety PLC because they are shutting down. We tried to decrease the traffic on the network to see if too much traffic could be the cause but we continue to have communication losses. I found some technote related to random loss ...