Posted By Bordeleau Nov 08, 2022 11:44:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Thank you for you response 'fuzzy logic'. Luckily I only need 4 preset speeds, but in any case, like you said I'll still be needing to add another DIG IN(X) in order to use the Acc2 and Decel2. Thanks again, Chris ------------------------------ Bordeleau ----------------------------- ...
Posted By Bordeleau Nov 08, 2022 11:40:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Thank you for your response Mr. Hamilton. I know what I need to do now, have a good day. Thanks, Chris ------------------------------ Bordeleau ------------------------------
Posted By Bordeleau Oct 31, 2022 03:38:00 PM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Yes, I am aware that a Dig In (X) can only be set to one function at a time. My question is to more or less to know if the PF70 functions like the PF40 with preset speeds and Acc2 and Dec2. Here is an image to help clarify a little. The image shows how both decel's affect different preset speeds. ...
Posted By Bordeleau Oct 28, 2022 10:16:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hello everyone, I have a question about the PF70's Accel 2 and Decel 2 parameter. From what I've found in the User Manual. The only way to use decel 2 on a PF70 is to have a Digital Input parameter (361 to 366) set to value 20 (for Accel 2 & Decel 2) or 22 ( for Decel 2 only). I could also be using ...