Posted By Davidson Oct 11, 2025 12:27:06 PM
Found In Egroup: Automation Control
\ view thread
Yes it is the same model and firmware revision the only thing that has changed is the ip address. the model we are using is an 1756-l75 rev 20.55. the new device is reachable, i can discover it in rslinx and can ping it. When i change the path in the dialog box i just immediately get an ioi syntax error, ...
Posted By Davidson Oct 08, 2025 10:42:00 AM
Found In Egroup: Automation Control
\ view thread
I'm trying to update an ip address for a CIP data table read message. The old message path was 1,3,2,10.24.37.201,1,0 and the new path im trying to put in is 1,3,2,10.25.5.201,1,0. However i am getting an IOI syntax error upon doing so. The only change that was made was to the ip address. We are using ...