Posted By Rodrigues da Silva Aug 21, 2023 10:44:13 AM
Found In Egroup: Networks
\ view thread
Dear Philip, Indeed, the limitations connections seems to be 128. Each CLX controllers process about 240 tags through EitherNet/IP communication and so I belive the I/O data capacity of 1000 words should suit the requirement. Thank you once again ------------------------------ Rodrigues da ...
Posted By Rodrigues da Silva Aug 21, 2023 04:08:00 AM
Found In Egroup: Networks
\ view thread
Dear All, I've accessing the feasability to have 3 PLC's (1756-L71) using each 1 EtheNet/IP modules (1756-EN2TR) connected to 1 Yokogawa Ethernet communication module (ALE111). However I'm unclear about the it. Thanks ------------------------------ Rodrigues da Silva ------------------ ...
Posted By Rodrigues da Silva Aug 21, 2023 03:46:00 AM
Found In Egroup: Networks
\ view thread
Hello Philip, Thank you for the valuable and educative answer. The problem was resolved upon the following: switched PSU off removed and re-inserted all the cards on the rack performed online program download Still unclear what initially caused the I/O cards lost the hart parameters and configiuration ...
Posted By Rodrigues da Silva Aug 17, 2023 05:09:26 AM
Found In Egroup: Networks
\ view thread
Hi Navaneeth, Thank you for the reply and the clarification. So I've to subscribe (pay) the RSNetWorx to be able to download from Rockwell Website? Unfortunatelly Offshore core crew does not have that and the Unit is down since days because if this PLC issue. Thanks ------------------------------ ...
Posted By Rodrigues da Silva Aug 16, 2023 11:32:00 AM
Found In Library: Networks
Posted By Rodrigues da Silva Aug 16, 2023 11:32:00 AM
Found In Egroup: Networks
\ view thread
Hello All, I've observed that all the I/O IF16H and OF8H installed on 1 backplane rack lost their hart parameters. Upon download the back up program the control module properties shows the code 16#0304 wich indicate that the module is not configured to send scheduled data.To use the RSNetWorx software ...