List of Contributions

Daniel O'Kelly

Contact Details

Daniel O'Kelly


My Content

1 to 20 of 50+ total
Posted By Daniel O'Kelly Apr 30, 2024 01:46:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hello Fells, It sounds like the NTC or wiring has become faulty. This drive will need to go to your nearest repair shop and these parts are not field replaceable.
Posted By Daniel O'Kelly Jan 10, 2024 06:02:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
It looks like all versions before 6.119 for Series A have been retired. It might be worth your while trying the latest version. The fault may have been rectified in this version. Not much mentioned in the release notes. It sounds to me like it might not be the module mentioned causing the fault ...
Posted By Daniel O'Kelly Jan 10, 2024 04:05:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hello M R What firmware version are you trying to download? Thanks ------------------------------ Daniel O'Kelly ------------------------------
Posted By Daniel O'Kelly Jan 05, 2024 08:06:00 AM
Found In Egroup: Advanced Software
\ view thread
Hi Rahul, The best thing to do would be call customer care in your area. Follow link and enter your location and country to get the correct phone number. Customer Care There is a software portal but I am not sure how easy it would be to upgrade your package on this website. Software Portal ...
Posted By Daniel O'Kelly Jan 05, 2024 07:08:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hi pmkg, I has been a while since I have done this. Check parameter 300 is set to Hz. I think if you write value into the DINT and see if you can get a 60Hz speed ref in Parameter 2. The you could use the SCP (scale with parameters) Add on Instruction you can scale up the Real value to ...
Posted By Daniel O'Kelly Jan 04, 2024 09:21:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Chapter 5 page 55 of the manual I sent earlier explains. Is the tag you are writing to a REAL? Thanks ------------------------------ Daniel O'Kelly ------------------------------
Posted By Daniel O'Kelly Jan 04, 2024 08:31:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hi pmkg, I don't think this parameter will give you the speed ref. Commanded speed ref should be updated in Parameter 2, when you change your value from 60 to 50 this parameter should reflect that change. The Output frequency which the drives is reaching will be parameter 1. Thanks ...
Posted By Daniel O'Kelly Jan 04, 2024 05:11:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hi pmkg, There is a manual available to help with this set up. 750 Series on DNET What is parameter 545 Set to. This will need to be set to the port with the DNet card. Writing to the correct tag should then update the speed ref. I hope this helps. ...
Posted By Daniel O'Kelly Dec 04, 2023 09:56:09 AM
Found In Egroup: Automation Control
\ view thread
Hi Chuck, I think you add a new function block per VSD and once you do this you will add a different IP address for it's respective VSD. Thanks ------------------------------ Daniel O'Kelly ------------------------------
Posted By Daniel O'Kelly Nov 30, 2023 03:58:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hello Lelen, Can you provide some more information on the PF7000. Do you know what firmware revision it VSD is on? Do you know is it a Classic or ForGE? Is it one PF7000 VSD or two? Thanks ------------------------------ Daniel O'Kelly ------------------------------
Posted By Daniel O'Kelly Nov 17, 2023 02:42:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hi Ali, This can happen if the drive has Auxiliary Power Supply, 20-750-APS and input power is off and start command is issued, or customer just powered on the Auxiliary Power Supply, 20-750-APS and keeps the main Power Supply off from the drive. Thanks ------------------------------ ...
Posted By Daniel O'Kelly Nov 16, 2023 05:19:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hi Ali, Does it happen every time you power up? The attached file did not have the drive config. Can you confirm what parameter 189, 321, 450 and 454 please? Thanks ------------------------------ Daniel O'Kelly ------------------------------
Posted By Daniel O'Kelly Nov 01, 2023 11:26:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hello Raja, Have a look at chapter 6 of the following manual. It should be possible to see P5 Torque Current feedback should be available using message instruction. PowerFlex 755 Drive Embedded EtherNet/IP Adapter Also Appendix F is useful in the following manual. P525 755 Programming ...
Posted By Daniel O'Kelly Oct 06, 2023 03:34:00 AM
Found In Egroup: Automation Control
\ view thread
Hi Ali, As far as I am aware these expansion modules are not programmable, they are general purpose and can be monitored in the Device monitor group. Please see QA37823 Thanks ------------------------------ Daniel O'Kelly ------------------------------
Posted By Daniel O'Kelly Oct 05, 2023 04:49:00 AM
Found In Egroup: Automation Control
\ view thread
Hi Ali, Check out parameters 202-204 There is a pdf at the bottom of the technote. QA37823 Thanks ------------------------------ Daniel O'Kelly ------------------------------
Posted By Daniel O'Kelly Oct 05, 2023 04:37:00 AM
Found In Egroup: Automation Control
\ view thread
Hello Ali, Do you want the output to change state when the E300 has tripped? What are you trying to achieve? Thanks ------------------------------ Daniel O'Kelly ------------------------------
Posted By Daniel O'Kelly Oct 02, 2023 03:35:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hello, The dwell time is not an actual programmable parameter but the time between movements. Taken from user manual chapter 9 Tuning. 5100 UM Hope this helps. ------------------------------ Daniel O'Kelly ------------------------------
Posted By Daniel O'Kelly Sep 27, 2023 10:27:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Hi Wagner, It is hard to say that previous wiring had an impact or what may have happened to cause this issue. You can send the drive to be repaired and will get a repair report as to what components have failed. Repair Services The above link will take you to the dedicated webpage ...
Posted By Daniel O'Kelly Sep 27, 2023 08:47:00 AM
Found In Egroup: Automation Control
\ view thread
Hello Sandoval, I think you are going to need RSLogix 500 and RSLinx. I will see if there are any other softwares that will work. Thanks ------------------------------ Daniel O'Kelly ------------------------------
Posted By Daniel O'Kelly Sep 26, 2023 08:55:00 AM
Found In Egroup: Drives, Motion Control & Low Voltage Products
\ view thread
Very strange behavior from the relays and I would be under the impression that this drives circuitry has become faulty, this is a NO NC set up and one of the relays (R1 or R3) should always be closed when measuring continuity from the Relay Common (R2) QA16190 Is the drive operational? Can ...