Posted By Robert B Apr 28, 2025 11:04:00 AM
Found In Egroup: Legacy
\ view thread
Update: After further troubleshooting and investigating we found that the power supply for the second expansion rack was undersized causing the fault to occur. We replaced it with a P4. We replaced the power supply in the primary rack but not the expansion rack.
Posted By Robert B Jan 27, 2025 10:37:00 AM
Found In Egroup: Legacy
\ view thread
Thanks for the very informative response Philip. A couple weeks go we indeed did put a power monitor on the power supply for 48 hours and observed no abnormalities with that. We do not use the 24VDC on the P4 Power Supply nor did we on the P2 that we had the same issue with both installed. ...
Posted By Robert B Jan 24, 2025 09:51:00 AM
Found In Egroup: Legacy
\ view thread
Thanks for the response Mitchell. The racks are connected by a ribbon cable (not positive on the part number off the top of my head either). I was starting to consider the cable, i ensured the connection was seated properly when i swapped the rack out but the cable itself has indeed not been replaced, ...
Posted By Robert B Jan 23, 2025 10:55:00 AM
Found In Egroup: Legacy
\ view thread
Hello everyone, new user here and i have been experiencing intermittent issues. We are using a SLC 5/05 Processor running 2 13 slot chassis with RSLogix 500. The fault we are receiving is a 21h fault (Remote power failure of an expansion I/O rack occurred). Our Network drops out for a split second causing ...