RE: Kinetix 5500 APR Fault Feedback Integrity Loss Subcode 5
Posted By
Fulk
Mar 25, 2026 10:44:03 AM
Found In
Egroup:
Drives, Motion Control & Low Voltage Products
\
view thread
Issue has been resolved. Problem was mechanical (bad cylinder) causing excessive movement during a certain part of the process. Nothing wrong with servo, cable, motor, connections, grounding, etc. -------------------------------------------
RE: Kinetix 5500 APR Fault Feedback Integrity Loss Subcode 5
Posted By
Fulk
Mar 19, 2026 07:29:10 AM
Found In
Egroup:
Drives, Motion Control & Low Voltage Products
\
view thread
Ok, I have deleted rung 11. See result tag below. -------------------------------------------
RE: Kinetix 5500 APR Fault Feedback Integrity Loss Subcode 5
Posted By
Fulk
Mar 18, 2026 11:15:12 AM
Found In
Egroup:
Drives, Motion Control & Low Voltage Products
\
view thread
@Batman @Vincent Bourrelly thanks for the replies. Cable length is about 40 ft. I added the DSLDiagnostics AOI - screenshots have 10 minute x axis. y axis from 0 to 110. I spoke with another controls engineer that has been working on the issue longer. For some background: Issue originated on ...
Kinetix 5500 APR Fault Feedback Integrity Loss Subcode 5
Posted By
Fulk
Mar 12, 2026 12:22:00 PM
Found In
Egroup:
Drives, Motion Control & Low Voltage Products
\
view thread
Getting this fault for a corner punching application every once in a while. There is a good amount of shock whenever it plunges, however we don't ever see this issue on the other 3 corners. Checked cable connections, have tried swapping drive and cables. PLC: 1756-L83ES firmware 36.011 Motor: VPL-B0753F-CJ14AA ...